FANUC I/O configuration: racks, slots, start points and signal types
How a FANUC controller ties its logical signals to real hardware, how to assign digital, group and UOP signals, and how to use simulated and forced I/O without leaving a trap for the next shift.
FANUC I/O configuration is the step that connects a signal name in a program, such as DI[12] or UO[1], to a real pin on a board or a bit in a network connection. Get it right and the program reads like the cell. Get it wrong, and a robot waits forever on a sensor that is on, or a gripper opens when a conveyor was meant to start. This guide covers the signal types on R-30iB and R-30iB Plus controllers, how rack, slot and start point work, how to assign and comment signals, and where simulated and forced I/O fit. Check your controller’s operator’s manual for your software version.
In short
FANUC robot I/O types
FANUC splits I/O into general-purpose signals, which you define, and specialized signals whose job is fixed.
| Signal | What it is | Remappable |
|---|---|---|
DI[i] / DO[i] |
General digital inputs and outputs | Yes |
GI[i] / GO[i] |
Group I/O: 2 to 16 digital points read or written as one number | Yes |
AI[i] / AO[i] |
Analog inputs and outputs, converted to digital values | Yes |
UI[i] / UO[i] |
Peripheral I/O (UOP): enables, start, program select, status | Yes |
SI[i] / SO[i] |
Operator panel buttons and lamps, including REMOTE | No |
RI[i] / RO[i] |
End effector I/O at the arm’s wrist connector, usually 8 in and 8 out depending on the model | No |
Safety signals such as the external emergency stop and the fence circuit are not in this list. They are wired to the controller’s safety inputs, which the controller’s maintenance manual describes, or carried by a safety network. They are not set up on these screens.
Logical and physical signals: rack, slot and start
The controller works with logical signals. Hardware has physical signals, numbered in1, in2 and so on for inputs and out1, out2 for outputs on each device. I/O assignment ties the two together with three numbers.
Rack is the kind of device. These are the common ones:
| Rack | Device |
|---|---|
| 0 | Process I/O board, I/O link connection unit |
| 1 to 15 | I/O Unit-MODEL A or MODEL B |
| 32 | I/O link slave interface |
| 34 | Flags (slot 1) and markers (slot 2) |
| 35 | Always ON |
| 36 | DCS Safe I/O, non-safety use |
| 48 | R-30iB Mate main board (CRMA15, CRMA16) |
| 81 to 84 | DeviceNet boards 1 to 4 |
| 89 | EtherNet/IP |
| 99, 100 | PROFINET controller, PROFINET device |
Slot is which device of that kind. For a process I/O board on the I/O link, the first connected device is slot 1. For a MODEL B unit it is the unit number set on its DIP switch. On networks such as EtherNet/IP, FANUC refers you to that network’s manual. Start is the first physical point the range maps onto, so DI[1-16] at rack 0, slot 1, start 21 puts DI[1] on in21.
If all assignments are deleted and the controller is power-cycled, it detects the connected hardware and builds the standard assignment again. Which signals end up as UOP depends on the UOP auto assignment setting, covered below.
How to assign digital I/O
-
Open the list
Press MENU, select 5 I/O, press F1, TYPE and choose Digital. F3, IN/OUT switches between inputs and outputs.
-
Open the configuration screen
Press F2, CONFIG. Each line is a range of signals with its RACK, SLOT, START and STAT.
-
Set the range
Put the cursor on RANGE and type the range you want. The screen splits lines to match.
-
Enter rack, slot and start
Type the values. STAT shows PEND when they are valid and INVAL when they aren't. F4, DELETE removes a line you don't need.
-
Power-cycle
The new assignment takes effect only after the controller restarts. STAT then reads ACTIV.
-
Save it
Back up the configuration to external storage, as FANUC's manual recommends after any I/O change.
FANUC’s manual asks you to check what each signal is used for before redefining it, because a moved output can drive the wrong device. It also warns that the first power-up after an I/O reassignment brings outputs up off, even with power failure recovery enabled.
Group I/O
A group input or output reads or writes 2 to 16 consecutive points as one number, which is how a PLC usually sends a part number, a recipe or a pallet layer. On the group screen you set RACK, SLOT, START PT and NUM PTS. A group can overlap points already used as DI or DO, but all of its points have to be on one board, and it can’t include an output that is part of a complementary pair.
Peripheral (UOP) assignment
UI and UO are configured on MENU, I/O, F1 TYPE, UOP, in the same rack, slot and start format. Full assignment gives 18 inputs and 20 outputs. Simple assignment uses 8 inputs and 4 outputs to free up points for general I/O, and FANUC ties UI[1] *IMSTP and UI[3] *SFSPD to the Always ON rack in that mode. The R-30iB default is Full; a Mate running LR Handling Tool defaults to Simple(CRMA16).
The UOP auto assignment setting on System Config needs care. Changing it asks whether to clear all I/O assignments, and answering YES deletes every assignment so the standard one is rebuilt at the next power-up. On a robot whose I/O was mapped to a PLC by hand, that is a long afternoon. Back up first. What each UI and UO does is in our FANUC UOP signals guide.
Comments, polarity and complementary outputs
From any list screen, press NEXT, then DETAIL, to open a signal’s detail screen. It holds:
- Comment. Name the signal for what it really does, such as “Gripper 1 closed” or “Clamp 2 extended”, not “Input 12”. The comment shows on the list screens and in program edit.
- Polarity. NORMAL turns the current on when the signal is on, INVERSE turns it on when the signal is off.
- Complementary. An odd-numbered output drives the next even one to the opposite state, for a double-solenoid valve.
UOP comments are written by the tool software. You can change them, but FANUC notes that the function stays the same.
Simulated I/O and forced outputs
Simulation lets you test a program before the cell is wired. A simulated input, marked S in the SIM column, ignores the real signal and takes whatever value is set on the screen. A simulated output changes internally but holds the physical output where it was. FANUC’s warning on both forced and simulated I/O is plain: the controller uses these signals to control other equipment, so check what a signal does before forcing or simulating it.
Four settings decide whether simulation becomes a problem later:
- Skip when simulated on a DI or RI detail screen lets a WAIT on that input time out after the Sim. Input Wait Delay set on System Config. FANUC says to use it only during test operation, never in production.
- Set if INPUT SIMULATED on System Config turns on a DO whenever any input is simulated. Wire it to a lamp or the PLC.
- Prog Select, Simulated I/O can refuse a production start while anything is simulated.
- TEST CYCLE, Digital/Analog I/O set to DISABLE simulates every signal at once.
The FCTN menu item UNSIM ALL I/O clears all of them. Allow Force I/O in AUTO mode on System Config decides whether signals can be set from the pendant in AUTO, and it is enabled by default.
Checking I/O from the pendant
The list screens are the quickest test of a mapping. Trigger a sensor and watch its DI change. Force a DO, with the cell clear and the person responsible for the machine aware, and confirm the right valve or PLC bit moves. The Interconnect screen can copy an RI, DI or SI to a DO, and the controller’s emergency stop states to DOs, which is useful when a PLC needs to see them.
Logic that maps or combines signals while programs run belongs in background logic, which our background logic guide covers. For I/O that comes from a PLC over the network, see our EtherNet/IP and Allen-Bradley guide.
Save the configuration
The I/O assignments, comments and I/O link settings live in DIOCFGSV.IO, which an All of above backup includes. Our FANUC robot backup guide covers taking and restoring one. When we change I/O on a robot, the backup comes first.
If a cell’s I/O no longer matches its drawings, or nobody is sure what a signal does any more, we sort out FANUC I/O on robots we didn’t build as well as our own. See our FANUC robot programming page, or call or text (818) 397-4809.
Common questions
- What do rack, slot and start mean in FANUC I/O?
- Rack is the kind of I/O device, such as 0 for a process I/O board, 48 for the R-30iB Mate main board or 89 for EtherNet/IP. Slot is which device of that kind, for example the first or second board on the I/O link, or the connection number on a network. Start is the first physical point on that device that the range of logical signals maps onto.
- Why does my new FANUC I/O assignment show PEND?
- PEND means the assignment is valid but not active yet. FANUC I/O assignments take effect only after the controller is power-cycled, and the status then changes to ACTIV. INVAL means a value you entered is wrong, and UNASG means nothing is assigned. FANUC also warns that on the first power-up after reassigning I/O, outputs come up off even if power failure recovery is enabled.
- Can I change which pins the UOP signals use?
- Yes. Peripheral I/O, UI and UO, can be mapped to any rack, slot and start point on the UOP configuration screen, just like digital I/O. Robot I/O and operator panel I/O can't be remapped. Be careful with the UOP auto assignment setting on System Config: changing it offers to clear every I/O assignment so the standard one can be rebuilt at the next power-up.
- How do I find simulated I/O on a FANUC robot?
- On each I/O list screen, a signal marked S in the SIM column is simulated, and U is not. FANUC also provides a System Config output, Set if INPUT SIMULATED, that turns on a DO whenever any input is simulated, so a PLC or a light can show it. The FCTN menu item UNSIM ALL I/O releases every simulated signal at once, once you know why they were simulated.
- Where is the FANUC I/O configuration saved?
- In the file DIOCFGSV.IO, which holds the I/O assignments, the comments and the I/O link settings. It is part of an All of above backup and can also be saved on its own. FANUC recommends saving the configuration to external storage once it is set, and a loaded I/O configuration file needs a power cycle before it takes effect.
Sources
- FANUC America: Robot support and manuals (R-30iB/R-30iB Plus Operator's Manual Basic Function B-83284EN/12: chapter 3.1 to 3.7 I/O, peripheral I/O, I/O link screen, simulated input skip; 3.15 System config menu; 6.3.1 Test cycle; 6.4 Manual I/O control; via the Customer Resource Center)
- FANUC America: EtherNet/IP for robot controllers (digital, group, UOP and analog I/O over EtherNet/IP)