FANUC SRVO-068 DTERR alarm: pulsecoder data errors and what to check
What the serial pulsecoder alarms mean, how to tell one bad axis from a shared fault, the order FANUC gives for checking cables, grounds and parts, and why a pulsecoder swap ends with mastering.
FANUC SRVO-068 is the DTERR alarm: the controller asked a serial pulsecoder for its data and got nothing back. The pulsecoder is the encoder on each axis motor, and the robot can’t run an axis it can’t read, so the controller stops it. SRVO-069 CRCERR and SRVO-070 STBERR are the same exchange going wrong in other ways. This guide covers what each alarm means, the order FANUC gives for checking them, and why replacing a pulsecoder or cable usually ends with mastering. It follows R-30iB family controllers. The maintenance manuals for your controller and robot are the reference.
In short
What does SRVO-068 DTERR mean?
Every axis motor on a FANUC arm has a serial pulsecoder. It reports the motor’s position over a serial link that runs through the robot’s internal cables and the robot connection cable to the servo amplifier in the controller. The amplifier sends a request, and the pulsecoder answers with its data.
FANUC’s maintenance manual describes SRVO-068 DTERR as the serial pulsecoder not returning serial data in response to that request. The alarm reads like SRVO-068 DTERR alarm (Grp:1 Ax:3), which is group 1, axis 3. Without that data the servo system has no position for the axis.
SRVO-069 CRCERR, SRVO-070 STBERR and the related pulsecoder alarms
These alarms often post together, and FANUC’s manual says which ones to trust when they do.
| Alarm | FANUC’s explanation | FANUC’s action |
|---|---|---|
SRVO-068 DTERR alarm |
The serial pulsecoder doesn’t return serial data in response to a request | Connectors and shield ground first, then parts in order (below) |
SRVO-069 CRCERR alarm |
The serial data was disturbed during communication | Same as SRVO-068 |
SRVO-070 STBERR alarm |
The start and stop bits of the serial data are abnormal | Same as SRVO-068 |
SRVO-071 SPHAL alarm |
The feedback speed is abnormally high | Same as SRVO-068. Posted with SRVO-064 PHAL, it isn’t the main cause |
SRVO-064 PHAL alarm |
The phase of the pulses from the pulsecoder is abnormal | Replace the pulsecoder, but FANUC notes PHAL can come along with DTERR, CRCERR or STBERR with no real phase fault |
SRVO-073 CMAL alarm |
The pulsecoder is likely abnormal, or it malfunctioned because of noise | Check the controller earth and the cable ground connections, reset the pulse count, then replace parts |
SRVO-072 PMAL and SRVO-074 LDAL |
The pulsecoder is likely abnormal, or the LED inside it is broken | Replace the pulsecoder and master the robot |
As a working rule, DTERR means nothing came back: a conductor or connector that isn’t making contact, or a pulsecoder that has stopped answering. CRCERR and STBERR mean something came back garbled, which fits a damaged conductor, a poor shield ground or electrical noise. That is a reading of what the codes describe, not a FANUC rule, and FANUC’s checks are the same for all three.
Is it one axis or all of them?
The Grp and Ax numbers name the pulsecoder. To see every axis at once, open the axis status screens: MENU, 0 NEXT, 4 STATUS, F1 TYPE, Axis, then STATUS2. That page shows a pulsecoder alarm status word for each axis, with a history field beside it. FANUC’s table in the controller manual names the bits, including DTERR, CRCERR, STBERR, BLAL and BZAL.
The pattern narrows the search. One axis alone points at that axis’s own pulsecoder, motor and the internal cable that runs to it. Several axes at once point at what they share: the robot connection cable, its connectors, its shield ground and the amplifier. That follows from how the signals are routed, so treat it as a starting point rather than a verdict. On a robot with an extended axis or a second motion group, check the group number before you start pulling cables.
What to check for SRVO-068, in FANUC’s order
FANUC’s maintenance manual gives one list of actions for SRVO-068 and refers SRVO-069 and SRVO-070 to it. The steps below follow that list, with one visual check of the cable added before any parts are ordered. The connector names are from the R-30iB Mate manual. Other controllers use different names, so work from the manual and drawings for yours.
-
Write down the alarm group
Record every alarm posted in the same second, the Grp and Ax numbers, and what the robot was doing. Photograph the STATUS2 page.
-
Check the connectors
With the power off and locked out, make sure the robot connection cable is fully seated at the servo amplifier (CRF8 on the R-30iB Mate 6-axis amplifier) and on the motor side. Look for bent or pushed-back pins.
-
Check the shield ground
FANUC says to check that the robot connection cable's shield is grounded securely in the cabinet. For CMAL, also check the controller earth and the cable grounds at the grounding plate.
-
Look at the cable
Walk the robot connection cable from the controller to the robot. Look for cuts, kinks, crush damage, and places where it was pinched by a guard or run over.
-
Then parts, in FANUC's order
The manual's order is the pulsecoder, the servo amplifier, the robot connection cable, then the internal cable of the robot. These are FANUC parts and, inside the arm, FANUC service work.
On many FANUC arms the pulsecoder is built into the motor. FANUC’s M-710iC manual says plainly that if the pulsecoder is abnormal, the motor is replaced. That makes the first four checks worth doing properly before anyone orders a motor.
When DTERR comes and goes
An alarm that clears with RESET and returns days later is the hard kind. FANUC’s mechanical troubleshooting table lists an intermittent break in a pulsecoder wire, in a part of the arm that moves, among the causes of trouble on the axis. A conductor like that can work in one pose and open in another.
Record the program, the line and the robot’s pose each time it posts. If it lines up with one motion, the cable that flexes during that motion is the first suspect, inside the arm or in the dress outside it. Also look at what changed nearby: a new drive, weld cables or power wiring run alongside the robot connection cable. FANUC lists noise as a cause of CMAL, and the fix it gives is grounding.
Why a pulsecoder swap means mastering again
Mastering ties each axis’s joint angle to its pulsecoder count. FANUC’s controller manual lists pulsecoder, motor, reducer or arm replacement as reasons mastering must be done, and says quick mastering can’t be used after a pulsecoder is replaced. That axis needs fixture position, zero position or single axis mastering. Our FANUC robot mastering guide compares the methods.
There is a second trap. FANUC notes that while parts for one axis are being replaced, the pulsecoder cables of other axes can be disconnected, and those axes post BZAL. Its answer is quick mastering for the axes that got BZAL, then single axis mastering for the axis whose part was replaced. The BZAL recovery steps are in our SRVO-062 BZAL guide. After a pulsecoder exchange, SRVO-038 Pulse mismatch can also appear, and FANUC’s action for it ends with mastering the robot.
Before production, check the robot against a known reference position and the witness marks, and step the program through in T1 at low speed. Then take a new backup so the new mastering data is saved off the robot. Our FANUC robot backup guide covers what to save.
The same alarms on a line tracking encoder
Conveyor tracking uses its own pulsecoder, wired to a line tracking board, and it has its own versions of these alarms: SRVO-090 DTERR alarm (Track enc:i), SRVO-091 CRCERR and SRVO-092 STBERR. FANUC’s actions are to check the cable at both ends, check that its shield is grounded at the grounding plate, then replace the encoder, the cable or the line tracking board. The arm’s pulsecoders aren’t involved, so robot mastering isn’t either, though a replaced encoder is worth checking against the tracking setup before production. Tracking setup is covered in our iRPickTool line tracking guide.
When to call FANUC, and when to call us
FANUC’s mechanical unit manual says alarms like PHAL, DTERR, CRCERR, STBERR and SPHAL may mean trouble with the pulsecoder, and to contact your FANUC representative. Replacing a pulsecoder, a motor or an internal cable is mechanical work on the arm, and that is FANUC’s service group.
The work around it is ours. We work on FANUC robots other companies installed as well as the cells we build in Fontana, CA: reading the alarm history, checking connectors, grounds and routing on the cell side, taking the backup, and checking mastering and programs once the part is in. Call or text (818) 397-4809 with the robot and controller model, the full alarm text including the Grp and Ax numbers, and a photo of the STATUS2 page. What a service job looks like is on our FANUC robot service page, and the other common alarms are in our FANUC alarm codes guide.
Common questions
- Can I reset SRVO-068 and keep running?
- If the alarm clears with RESET and stays clear, the pulsecoder answered again, so the fault is intermittent rather than gone. Write down the axis, the time and what the robot was doing, and check the connectors, the shield ground and the cable at the next planned stop. If it posts again straight away, the link is still down and the robot should not run until the cause is found.
- Does SRVO-068 DTERR mean the motor is bad?
- Not on its own. FANUC's maintenance manual lists connector and shield ground checks before any part replacement, then the pulsecoder, the servo amplifier and the cables. On many FANUC arms the pulsecoder is part of the motor, so a pulsecoder replacement means a motor, which is why the cheap checks should come first.
- Do I have to remaster after fixing a DTERR alarm?
- It depends on what was done. Reseating a connector with the battery backup intact needs no mastering. If a pulsecoder lost its battery backup while a cable was unplugged, SRVO-062 BZAL posts and that axis needs at least quick mastering. If a pulsecoder or motor was replaced, FANUC says quick mastering can't be used, so that axis needs fixture, zero position or single axis mastering.
- What is the difference between SRVO-068 and SRVO-062?
- SRVO-062 BZAL is about the battery that keeps each pulsecoder's revolution count while the controller is off. The count is lost and the robot needs mastering. SRVO-068 DTERR is about the data link between the pulsecoder and the controller: the pulsecoder didn't answer a request. One is fixed with batteries and mastering, the other with connectors, grounds, cables or parts.
- Can CalWest repair a FANUC pulsecoder?
- Replacing a pulsecoder, motor or internal cable inside the arm is work for FANUC's service group, and we'll say so plainly. We handle the cell side: reading the alarms, checking connectors, grounding and cable routing, taking a backup, and checking mastering and programs after the part is replaced. Call or text (818) 397-4809 with the robot model and the full alarm text.
Sources
- FANUC R-30iB Mate/R-30iB Mate Plus controller maintenance manual, B-83525EN/07: troubleshooting SRVO-064 to SRVO-075 and SRVO-090 to SRVO-092 (hosted by Haas Automation)
- FANUC R-30iB/R-30iB Plus controller operator's manual (Basic Function), B-83284EN/10: appendix B.2 mastering and B.4 robot axis status (hosted by RoboChallenge)
- FANUC M-710iC/20L mechanical unit operator's manual, B-82514EN/09: mastering and troubleshooting (hosted by Haas Automation)
- FANUC America: Robot support and manuals (Alarm Code List B-83284EN-1, via the Customer Resource Center)