FANUC SRVO-037 IMSTP input: why the robot's stop signal dropped
What the *IMSTP peripheral input is, how it differs from the hold and safety speed inputs, and how to trace an SRVO-037 back through the UOP screen, the I/O assignment and the PLC to whatever turned it off.
FANUC SRVO-037 is the IMSTP input alarm. The robot controller saw its immediate stop input, *IMSTP, turn off, so it posted the alarm, turned servo power off and stopped the robot and the program. The signal almost always comes from a PLC or another device outside the robot, which means the cause usually sits there too. This guide covers what the signal is, how it differs from the other stop inputs, and how to trace it back to whatever dropped it. Menu names are from R-30iB and R-30iB Plus controllers.
In short
What is the *IMSTP signal on a FANUC robot?
*IMSTP is the immediate stop signal, the first of the peripheral I/O inputs, UI[1]. FANUC’s manual describes it as always enabled and on in normal status. The asterisk marks it as a reverse signal, and FANUC’s input specification calls for a normally closed contact. When the signal turns off, FANUC’s manual says three things happen: an alarm is posted and servo power turns off, the robot stops immediately, and program execution stops.
FANUC is just as clear about what it is not. The manual warns that *IMSTP is controlled by software and says to use the external emergency stop for safety-critical processing. The maintenance manual says not to use *IMSTP as a safety relevant signal at all. People are protected by the hard-wired e-stop and fence circuits, covered in our SRVO-007 external e-stop guide. *IMSTP is how a PLC stops the robot for process reasons.
How *IMSTP differs from *HOLD and *SFSPD
FANUC lists three UOP inputs as always enabled, and each one acts when it turns off. ENBL also stops motion when it drops. Each stops the robot differently.
| Input | What FANUC’s manual says happens when it turns off |
|---|---|
UI[1] *IMSTP |
Alarm posted, servo power off, robot and program stop immediately: SRVO-037 |
UI[2] *HOLD |
The robot decelerates to a stop and the program is held. An alarm and servo power off happen only if Break on hold is enabled on the general setup screen |
UI[3] *SFSPD |
The motion decelerates and stops, the program stops, and the speed override drops to the fence override value. It is normally wired to the safety fence door |
UI[8] ENBL |
Jogging and motion programs are inhibited, and a running program is halted |
If the robot stopped without SRVO-037 in the alarm history, *IMSTP wasn’t the input that stopped it. Our FANUC UOP signals guide covers the rest of the peripheral inputs and outputs.
Where does *IMSTP come from?
Open the UOP screen: MENU, 5 I/O, F1 TYPE, UOP. The list shows each UI signal with its current state. If UI[1] reads OFF, the controller isn’t seeing the signal. Press F2, CONFIG to see the rack, slot and start point that UI[1] is assigned to. The rack tells you what kind of device the signal arrives on. FANUC’s list includes:
- Rack 0: process I/O board or I/O link connection unit
- Rack 48: the R-30iB Mate main board connectors, CRMA15 and CRMA16
- Rack 89: EtherNet/IP
- Racks 81 to 84: DeviceNet boards
- Racks 66 and 67: PROFIBUS-DP master and slave
A hard-wired rack means a wire, a terminal and a PLC output card. A network rack means the signal is a bit in the PLC’s output data, and the network connection is part of the path. Our FANUC I/O configuration guide explains rack, slot and start point in more detail, and the PLC side of an EtherNet/IP link is in our FANUC EtherNet/IP guide.
How to trace an SRVO-037 alarm
-
Read the alarm history
Open MENU, ALARM, F3 HIST. Note the time of SRVO-037 and anything posted with it, such as an I/O communication (PRIO) alarm or another stop alarm.
-
Check UI[1] on the robot
On the UOP screen, see whether UI[1] is ON or OFF right now, and note its rack and slot from F2 CONFIG.
-
Check the PLC output
Find the PLC output or output bit that drives *IMSTP. If the PLC has it off, the cause is in the PLC logic: a line stop, a fault, a mode change, or a handshake condition that isn't met.
-
If the PLC has it on, check the path
The robot isn't receiving what the PLC sends. On a wired signal, check the terminals, the output card and the I/O assignment. On a network, check the connection status on both ends.
-
Fix the cause, then reset
FANUC's remedy is to turn the *IMSTP signal on. With UI[1] back ON, press RESET on the pendant or send the reset input from the PLC.
A recent change is a common thread. A PLC program download, a replaced I/O card, an I/O assignment edited on the robot, or a controller restored from another robot’s backup can all leave UI[1] pointed somewhere that isn’t on. If the alarm started right after work like that, compare the UOP assignment and the PLC tags with the cell’s documentation before anything else.
SRVO-037 that comes and goes
A robot that stops with SRVO-037 now and then, and runs fine after a reset, has a signal that is dropping for a moment. On a wired signal that points at a loose terminal or a failing contact somewhere in the path. Over a network, it points at the connection or the PLC logic. A few places to look:
- I/O communication alarms in the robot’s history at the same time stamp.
- The PLC’s own fault log and the connection diagnostics for the robot.
- PLC logic that can turn the bit off for one scan, such as a heartbeat or a reset sequence.
Trending the bit in the PLC alongside the time of each stop usually shows which side dropped it. Our robot won’t run in auto guide covers the other UOP conditions that keep a robot from starting.
Getting help
When the PLC was written by someone who is long gone, SRVO-037 can take a while to run down. We read FANUC UOP setups and Allen-Bradley and Siemens PLC logic, on cells other companies installed as well as the ones we build in Fontana, CA. Call or text (818) 397-4809 with the robot and controller model, a photo of the UOP screen and its CONFIG page, and the alarm history. What a service job looks like is on our FANUC robot service page, and the other common alarms are in our FANUC alarm codes guide.
Common questions
- What does IMSTP stand for on a FANUC robot?
- It is the immediate stop input, UI[1] in the peripheral I/O (UOP) signals. The asterisk in *IMSTP marks it as a signal that is on in normal running and acts when it turns off. FANUC's manual says that when it goes off, an alarm is posted, servo power turns off, and the robot and its program stop immediately.
- Is *IMSTP a safety signal?
- No. FANUC's manuals say *IMSTP is controlled by software, that it should not be used as a safety relevant signal, and that the external emergency stop circuit is the one to use for safety-critical stops. In a well-designed cell, e-stops, gates and light curtains act through the hard-wired safety circuits, and *IMSTP is a process stop from the PLC on top of them.
- Can I jumper *IMSTP to clear SRVO-037?
- No. In a cell that uses it, *IMSTP is part of the stop logic the integrator designed, usually the PLC's way of stopping the robot when something else on the line has stopped. Defeating it hides the reason the PLC dropped it and can let the robot run when the rest of the line expects it to be stopped. Find out why the signal went off and fix that.
- Why does SRVO-037 happen at random with an EtherNet/IP PLC?
- When the UOP inputs come over a network, the network connection is part of the stop path. A connection that drops, a PLC that changes mode, or logic that turns the output off for a moment can all turn *IMSTP off. Look for I/O communication alarms posted at the same moment, then check the PLC's logic and the connection's diagnostics on both ends.
- How do I clear SRVO-037 after the cause is fixed?
- FANUC's remedy is to turn the *IMSTP signal back on. Once UI[1] shows ON on the UOP screen, press RESET on the teach pendant or send the reset input from the PLC. If the alarm returns straight away, the signal is still off or dropping again, and the trace should continue from the UOP screen.